Homepage Fill Out a Valid Florida Energy Template
Table of Contents

In Florida, individuals engaged in constructing or modifying residential buildings are required to adhere to specific regulations to ensure energy conservation. These requirements are encapsulated in the detailed content of the Florida Energy form, which mandates compliance with Section 402 of the Florida Building Code, Energy Conservation. It covers a broad spectrum of constructions, including single and multiple-family residences up to three stories, as well as additions, renovations, and the introduction of new heating, cooling, and water heating systems in existing buildings. The form utilizes a comprehensive approach, setting forth energy efficiency benchmarks that the construction must meet or surpass, as detailed in Tables 402A and 402B. Not only does it guide the selection of energy-efficient components by listing acceptable values for key features like glass area and insulation but it also outlines mandatory requirements for sealing, air leakage, and equipment efficiency. In cases where a building cannot meet these standards through this method, it may seek compliance under an alternative path offered by Section 405 of the Florida Building Code, Energy Conservation. Moreover, the form specifies exceptions and provides space for the identification of construction or renovation details, alongside requirements for certifications by the preparer and owner or owner's agent. This structured approach ensures that buildings not only strive for energy efficiency but also adhere to a code designed to promote sustainability and environmental responsibility in Florida's residential constructions.

Document Preview Example

FORMS

Scope: Compliance with Section 402 of the Florida Building Code, Energy Conservation, shall be demonstrated by the use of Form 402 for single- and multiple-family residences of three stones or less in height, additions to existing residential buildings, renovations to existing residential buildings, new heatingbcoolingJ and water heating systems in existing buildings, as applicable.To comply, a building must meet or exceed all of the energy efficiency requirements on Table 402A and all applica le manoatory requirements summarized in Table 402B of this form. If a building does not comply with this method or Alternate Form 402, it may still comply under Section 405 of the Florida Building Code, Energy Conservation.

General Instructions:

constrLJcti.<m which incorporates any of the following features cannot comply using this method: glass areas in excess of 20 pen:::ent of conditioned floor area, electric resistance located in attics. Additions:::; 600 sq .ft., renovations and equipment change outs may comply by this method with exceptions given.

applicable spaces of the "To Be Installed" column on Table 402A with the information requested. All "To Be Installed" values must be equal to or more efficient than the

"To Be Installed" column information.

402B and check each box to indicate your intent to comply with all applicable items.

"Prepared By" certification statement at the bottom of page 1. The owner or owner's agent must also sign and date the form.

1.New construction, addition, or existing building

2.Single-family detached or multiple-family attached

3.If multiple-family-No. of units covered by this submission

4.Is this a worst case? (yes/no)

5.Conditioned floor area (sq. ft.)

6.Glass type and area:

Please Print

CK

1.

2.

3.

4.

5.

U-factor

b.SHGC

7.Percentage of glass to floor area

8.Floor type, area or perimeter, and insulation:

6a.

6b.

6c.

sq. ft.

7.

%

Slab-on-grade (R-value) b. Wood, raised (R-value)

Wood, common (R-value)

d.Concrete, raised (R-value)

common (R-value)

9.Wall type, area and insulation:

l. Masonry (Insulation R-value) Wood frame (Insulation R-value)

b. Adjacent: 1. Masonry (Insulation R-value) Wood frame (Insulation R-value)

10. Ceiling type, area and insulation:

Under attic (Insulation R-value)

Single assembly (Insulation R-value)

11.Air distribution system: Duct insulation, location, Qn

Duct location, insulation b. AHU location

Qn, Test report attached(< 0.03; yes/no)

12. Cooling system:

Type

b.Efficiency

13.Heating system:

Type

b. Efficiency

Sa. R:::

lin. ft.

8b. R:::

sq. ft.

ac. R=

sq. ft.

8d. R:::::

sq. ft.

ae. A=

sq. ft.

9a-i. A=

sq. ft.

9a-2.

R=

sq. ft.

9b-1.

R::::

sq. ft.

9b-2.

R::::

sq. ft.

10a. R=

sq. ft.

 

10b. R-

 

sq. ft.

11a. R:::: ____

 

 

11b. ----------------

 

11 c.Test report attached? Yes

No

14.

HVAC sizing calculation: attached

14. Yes No

 

 

15.

Hot water system:

 

 

 

15a.

 

 

15b.

plans and specifications covered by the calculation are in compliance with the Florida Review of plans and specifications covered by this calculation indicates compliance with the Florida Energy Code. Before construction is completed, this building will be inspected for compliance in accordance with Section 553.908, F.S.

DATE: ____

CODE OFFICIAL:___________________.

rnrtiht エィセエエィゥッ@building is in compliance with the Florida Energy Code:

DATE: ____

C.4

2010 FLORIDA BUILDING CODE- ENERGY CONSERVATION

FORMS

TABLE402A

BUILDING COMPONENT

Windows (see Note 2):

Skvliahts

セイウZ@Exterior door U-Factor Floors: Slab-on-grade

Over unconditioned spaces (see Note 3) Walls- Ext. and Adj. (see Note 3):

Frame

Mass (see Note 3) Interior of wall: Exterior of wall:

Ceilings (see Notes 3 & 4)

Reflectance

Air distribution system (see Note 4)

Ductwork & air handling unit:

Unconditioned space

Conditioned space

Duct A-value

Air leakage On

Air conditionina svstems (see Note 5) Heating system

Heat pump (see Note 5)Cooling: Heating:

Gas furnace Oil furnace

Electric resistance: Not allowed (see Note 5)

Water heating system (storage type)

Electric (see Note

Gas fired (see Note 7):

Other (describe):

PERFORMANCE CRITERIA'

U-Factor < 0.65 SHGC=0.30 %of CFA <::: 20% U-Factor < 0.75 U-Factor < 0.65 No requirement R-13

R-13

R-7.8

R-6

R=30

0.25

Not allowed

A-value<: 6

On セPNPS@

SEER= 13.0

SEER 13.0

HSPF = 7.7

AFUE78%

AFUE78%

40 gal: EF = 0.92

50 gal: EF = 0.90

40 gal: EF = 0.59

50 gal: EF 0.58

INSTALLED VALUES:

U-Factor=

SHGC=

%of CFA=

U-Factor=

R-Value =

A-Value

A-Value=

A-Value-

A-Value=

Test report

Attached?

Reflectance =

Yes/No

 

Location:

Test report

 

 

Attached?

 

Yes/No

R-Value

 

On=

 

SEER=

 

SEER=

 

HSPF=

 

AFUE=

 

AFUE=

 

Gallons

 

EF=

 

Gallons=

 

EF=

 

(1)Each component present in the As Proposed home must meet or exceed each of the applicable performance criteria in order to comply with this code using this method; otherwise Section 405 compliance must be used.

(2)Windows and doors qualifying as glazed fenestration areas must comply with both the maximum U-Factor and the maximum SHGC (solar Heat Gain Coefficient) criteria and have a maximum total window area equal to or less than 20% of the conditioned floor area (CFA); otherwise Section 405 must be used for compliance. Exception: Additions of 600 square feet (56 m2) or less may have a maximum glass to CFA of 50 percent.

(3)A-values are for insulation material only as applied in accordance with manufacturers' installation instructions. For mass walls, the "interior of wall" requirement must be met except if at least 50% of the R-6 insulation required for the "exterior of wall" is installed exterior of, or integral to, the wall.

(4)Ducts & AHU installed substantially leak free per Section 403.2.2.1. Test by Class 1 BERS rater required.

Exception: Ducts installed onto an existing air distribution system as part of an addition or renovation; duct must be R-6 installed per Sec. 503.2.7.2.

(5) For all conventional units with capacities greater than 30,000 Btu/hr. For other types of equipment, see Tables 503.2.3(1-8).

Exception: The prohibition on electric resistance heat does not apply to additions, renovations and new heating systems installed in existing buildings.

(6)For other electric storage volumes, minimum EF = 0.97-(0.00132 x volume).

(7)For other natural gas storage volumes, minimum EF =0.67-(0.0019 x volume).

TABLE 4028 MANDATORY REQUIREMENTS

 

 

COMPONENTS

SECTION

REQUIREMENTS

I

CHECK

 

 

To be caulked, gasketed, キ・。エィ・イウエイゥーセ・、@or otherwise sealed. Recessed lighting !C-rated as meeting ASTM E

 

 

Air leakage

402.4

283. Windows and doors= 0.30 cfm/sq.ft. Testing or visual inspection required. Fireplaces: gasketed doors &

 

 

 

 

outdoor combustion air.

 

 

Ceilings/knee walls

405.2.1

R-19 space permitting.

 

 

Programmable thermostat

403.1.1

Where forced-air furnace is primary system, programmable thermostat is required.

 

 

Air distribution system

403.2

Ducts in attics or on roofs insulated to R-8; other ducts R-6. Ducts tested to a. = 0.03 by a Class 1 BERS rater.

 

 

 

 

Heat trap required for vertical pipe risers. Comply with efficiencies in Table 403.4.3.2. Provide switch or clearly

 

 

Water heaters

403.4

marked circuit breaker (electric) or shutoff (gas). Circulating system pipes insulated to= R-2 +accessible manual

 

 

 

 

OFF switch.

 

 

 

 

Spas and heated pools must have vapor-retardant covers or a liquid cover or other means proven to reduce heat

 

 

Swimming pool &spas

403.9

loss except if 70% of heat from site-recovered energy. Off/timer switch required. Gas heaters minimum thermal

 

 

 

 

efficiency- 78% (82% after 4/16/13). Heat pump pool heaters minimum COP- 4.0.

 

 

 

 

Sizing calculation performed &attached. Minimum efficiencies per Tables 503.2.3. Equipment efficiency verification

 

 

Cooling/heating equipment

403.6

required. Special occasion cooling or heating capacity requires separate system or variable capacity system.

 

 

 

 

Electric heat >10kW must be divided into two or more stages.

 

 

Lighting equipment

404.1

At least 50% of permanently installed lighting fixtures shall be high-efficacy lamps.

 

 

2010 FLORIDA BUILDING CODE- ENERGY CONSERVATION

C.5

Document Overview

Fact Detail
Applicability Form 402 applies to single- and multiple-family residences of three stories or less, additions, renovations, and new or replaced heating, cooling, and water heating systems.
Compliance Requirement Compliance with Section 402 of the Florida Building Code, Energy Conservation, requires meeting energy efficiency requirements in Table 402A and mandatory requirements in Table 402B.
Excluded Features Construction with glass areas exceeding 20% of conditioned floor area or electric resistance heating in attics cannot use this compliance method.
Alternate Compliance Path If not compliant through Form 402 or Alternate Form 402, compliance must be demonstrated under Section 405 of the Florida Building Code, Energy Conservation.
Signature Requirement The form must be certified and signed by the prepared by individual and the owner or owner's agent.
Governing Law Section 553.908, F.S. outlines inspection requirements before construction completion to ensure compliance with the Florida Energy Code.
Special Provisions for Additions and Renovations Additions under 600 sq. ft., renovations, and equipment changes may comply using this form with certain exceptions.

Instructions on How to Fill Out Florida Energy

When preparing to complete the Florida Energy Form, it's essential to gather all relevant information about the building project in question. This form is designed to ensure that new constructions, additions, renovations, and the installation of new heating, cooling, and water heating systems in existing buildings comply with Section 402 of the Florida Building Code, Energy Conservation. The process requires accuracy in filling out the form to demonstrate compliance with energy efficiency requirements and applicable mandatory requirements. Here are the steps to guide you through the process:

  1. Identify the type of project you are working on (new construction, addition, or existing building) and specify whether it's a single-family detached or multiple-family attached residence. Also, indicate the number of units covered and whether this is a worst-case scenario.
  2. Enter the conditioned floor area in square feet.
  3. Provide detailed information about the glass used in the project, including type, area, U-factor, and Solar Heat Gain Coefficient (SHGC), along with the percentage of glass to floor area.
  4. Detail the floor type and area or perimeter, and specify the insulation R-value for slab-on-grade, wood (raised and common), and concrete (raised and common).
  5. List wall types (masonry and wood frame) and the respective area and insulation R-value for both exterior and adjacent walls.
  6. Fill in the ceiling type, area, and insulation R-value for areas under the attic and for single assembly ceilings.
  7. Document the air distribution system details, including duct insulation and location, air handling unit location, and if a test report is attached verifying duct leakage is below 0.03.
  8. Specify the cooling system type and efficiency, and do the same for the heating system.
  9. Complete information related to the hot water system, including specifying the type and energy factor for both 40 and 50-gallon capacities or other if applicable.
  10. Check if the HVAC sizing calculation is attached.
  11. Fill out Table 402A with the installed values for components like windows, skylights, exterior doors, floors, walls, ceilings, the air distribution system, air conditioning systems, heating systems, and the water heating system based on the performance criteria provided. Ensure that all "To Be Installed" values meet or exceed the designated efficiency requirements.
  12. Under Table 402B, ensure all mandatory requirements are met by checking each box to indicate compliance. This includes items related to air leakage, windows and doors, recessed lighting, fireplaces, ceiling insulation, programmable thermostats, duct insulation, water heaters, swimming pools and spas, equipment efficiency, and lighting equipment.
  13. Sign and date the "Prepared By" certification statement at the bottom of the first page of the form. This must be signed by the owner or the owner's agent to certify the accuracy of the information provided.

Upon successfully completing and submitting the Florida Energy Form, the next steps include a review of plans and specifications to ensure they comply with the Florida Energy Code. Before the construction process concludes, the building will undergo inspection to verify compliance with Section 553.908, Florida Statutes. This rigorous process ensures that buildings adhere to the state's energy conservation requirements, contributing to environmental sustainability and potentially reducing energy costs for occupants.

Listed Questions and Answers

What is the purpose of the Florida Energy Form?

The Florida Energy Form is designed to ensure that single- and multiple-family residences of three stories or less, as well as additions, renovations, and new heating, cooling, and water heating systems in existing buildings, comply with Section 402 of the Florida Building Code, Energy Conservation. The form verifies that a building meets or exceeds the specific energy efficiency requirements outlined in Tables 402A and 402B, contributing to energy conservation and efficiency in construction.

Can renovations and additions use the Florida Energy Form for compliance?

Yes, renovations and additions to existing residential buildings can use the Florida Energy Form for compliance, with certain exceptions. Additions of 600 square feet or less, renovations, and equipment change outs may comply using this form. However, constructions incorporating features such as glass areas exceeding 20 percent of the conditioned floor area and electric resistance heat located in attics may require alternative methods for compliance.

What are the steps for completing the form?

To complete the form, fill out the applicable spaces in the "To Be Installed" column on Table 402A with the required information. All "To Be Installed" values must be equal to or more efficient than those mentioned in the column. Then, complete Table 402B, indicating your intent to comply with all applicable mandatory requirements. Finally, the "Prepared By" certification at the bottom of page 1 must be signed, along with the owner or owner's agent’s signature and date, to certify compliance.

How does a building qualify under the glass area requirements mentioned in the form?

For a building to qualify under the glass area requirements, windows and doors that count as glazed fenestration areas must comply with both the maximum U-Factor and the maximum Solar Heat Gain Coefficient (SHGC) criteria. They must also have a total window area that is equal to or less than 20% of the conditioned floor area (CFA). Yet, an exception allows additions of 600 square feet or less to have a maximum glass to CFA ratio of 50 percent.

What happens if a building cannot comply with the Florida Energy Form?

If a building cannot comply with the requirements as stated in the Florida Energy Form or its alternate, compliance can still be achieved under Section 405 of the Florida Building Code, Energy Conservation. This section may provide alternative compliance paths for buildings with specific features or design elements that do not meet the standard requirements outlined in the form.

Are ducts and air handling units required to be tested for leaks?

Yes, ducts and air handling units (AHU) installed must be substantially leak free, as mandated by Section 403.2.2.1. Testing by a Class 1 BERS rater is required to demonstrate compliance. However, an exception is provided for ducts installed onto an existing air distribution system as part of an addition or renovation, where the duct must be insulated to R-6 as per Section 503.2.7.2, but may not require the same level of testing if adding onto an existing system.

Common mistakes

  1. Filling in the wrong performance criteria values for building components such as windows, walls, and HVAC systems is a common mistake. The form requires specific performance metrics like U-Factor and Solar Heat Gain Coefficient (SHGC) for windows, and efficiency values for heating and cooling systems. When these numbers aren't correct or are left blank, it may indicate that the installation doesn't meet the necessary energy efficiency requirements. For instance, windows and doors must comply with both the maximum U-Factor and SHGC criteria and adhere to a maximum total window area of less than 20% of the conditioned floor area, unless exceptions apply. Additionally, heating systems should not use electric resistance heat, with specified exceptions, to comply.

  2. Another error involves the insulation values and air sealing measures, which are crucial for compliance but often entered inaccurately. The form dictates the need for precise insulation R-values for different parts of the building like floors, walls, and ceilings, aligned with manufacturers' installation instructions. It also requires air sealing measures that aim to minimize air leakage, specifying requirements for different components such as recessed lighting and fireplaces. Incorrectly entered values can suggest a lack of compliance with mandatory energy conservation measures intended to ensure efficient energy use and occupant comfort.

  3. Not providing or incorrectly indicating the HVAC system sizing and testing results is a frequent mistake. The form insists on the attachment of HVAC sizing calculations and, where applicable, duct leakage test reports. These documents are vital to prove that the heating, ventilation, and air conditioning systems are appropriate for the building's size and that the ductwork does not leak excessively, thereby ensuring efficient operation. Failing to attach these documents or indicating "No" where "Yes" is accurate can lead to non-compliance with requirements that aim for energy conservation.

  4. Overlooking the signing and dating of the form by the owner or the owner's agent is another common oversight. The "Prepared By" certification statement at the bottom of the first page is a mandatory requirement that must be completed to validate the form. This signature verifies that all the information provided is accurate to the best of the signatory's knowledge and that the building plans comply with the Florida Energy Code. Ignoring this final but crucial step undermines the form's validity and can delay the approval process.

  • Entering incorrect or overly optimistic "To Be Installed" values in Table 402A for components such as windows, insulation, and HVAC systems can imply that the building's design is more energy-efficient than it actually is.
  • Failing to check off each mandatory requirement in Table 402B signifies that these critical energy conservation measures may not be implemented in the building's design or construction.
  • Omitting the attachment of required documents such as HVAC sizing calculations and duct leakage test reports extends the possibility that the HVAC system may not suit the building's needs or that ductwork leaks excessively, leading to inefficiencies.
  • Forgetting to sign and date the form means overlooking the certification that all entered information and attached documents are accurate and comply with the Florida Energy Code, leading to potential delays in the verification process.

Documents used along the form

Documents and forms are essential tools for navigating the specifics of building codes and regulations related to energy conservation in Florida. Along with the Florida Energy Form, which provides a detailed approach to ensuring buildings comply with Section 402 of the Florida Building Code for Energy Conservation, there are several other documents and forms that can assist homeowners, contractors, and professionals in the field. Here is a list of up to 10 such documents that often accompany the Florida Energy Form:

  • Building Permit Application: This form initiates the process for legal construction, alteration, or renovation of a building, ensuring that all work complies with local codes and standards.
  • Owner Builder Affidavit: Used by property owners opting to act as their own contractor, this document confirms their understanding of the responsibilities and regulations involved.
  • Electrical Permit Application: Separate from the general building permit, this focuses on the installation, modification, or repair of electrical systems within a project.
  • Product Approval/Listing Form: Validates that specific products used in construction meet the Florida Building Code's stringent requirements for energy efficiency and safety.
  • Notice of Commencement: Filed before the start of a construction project, this form notifies parties of the commencement date, which can affect mechanics' lien laws in Florida.
  • Insulation Certification Form: Certifies that the insulation installed in a building project meets or exceeds the required R-values for energy efficiency as specified in the Florida Energy Code.
  • HVAC System Design and Sizing Calculation Forms: Demonstrate that heating, ventilation, and air conditioning systems are appropriately sized for the building to ensure energy efficiency.
  • Window and Door Schedule/Form: Provides details about the U-factor and Solar Heat Gain Coefficient (SHGC) for windows and doors, confirming compliance with energy performance criteria.
  • Blower Door Test Results: Documents the air tightness of a building to ensure it meets the Florida Building Code for energy conservation, particularly Section 402 regarding air leakage.
  • Duct Leakage Test Certificate: Similar to the blower door test, but specifically for the ductwork, ensuring the heating and cooling systems do not leak, saving energy.

Together, these documents form a comprehensive toolkit for achieving and proving compliance with the Florida Building Code, Energy Conservation requirements. From initiating a project with permit applications, to verifying specific components like insulation and HVAC systems, to final compliance verification through testing, each document has a crucial role in the construction and renovation process. Understanding the purpose and requirement of each can significantly streamline the process for all parties involved.

Similar forms

The Florida Energy Form is similar to the California Energy Commission's Title 24 Energy Efficiency Standards. Just like the Florida Energy Form, California's standards require detailed documentation of a building's energy features, including insulation, windows, HVAC systems, and water heating systems, to ensure compliance with the state's energy conservation requirements. Both set comprehensive performance criteria for new construction, additions, and renovations, specifying values for U-factor, SHGC (Solar Heat Gain Coefficient), and minimum R-values for insulation in various building components. Additionally, each mandates the installation of energy-efficient mechanical systems and lighting, aiming to reduce energy consumption across residential buildings.

Another document that shares similarities with the Florida Energy Form is the Residential Energy Services Network’s (RESNET) Home Energy Rating System (HERS) Index. The HERS Index is a nationally recognized system for inspecting and calculating a home's energy performance. While the HERS Index itself is not a form, it requires data similar to what is found in the Florida Energy Form, such as insulation levels, HVAC system efficiency, and total window area relative to floor area. Both systems are designed to improve the energy efficiency of homes, but while the Florida Energy Form is a compliance tool under the Florida Building Code, the HERS Index offers a standardized rating system that can be used for comparing the energy performance of homes nationwide.

Dos and Don'ts

When filling out the Florida Energy form, it's essential to pay close attention to the details to ensure compliance with the Florida Building Code, Energy Conservation. Below are some tips on what you should and shouldn't do while completing this form:

Do's:

  • Ensure accuracy: Double-check the "To Be Installed" column on Table 402A to fill in the specific details as accurately as possible. All installed values should meet or exceed the minimum efficiency requirements outlined.
  • Verify compliance: Confirm that every component of your building complies with the mandatory requirements summarized in Table 402B, and indicate your intent to comply by checking each box.
  • Sign the form: The "Prepared By" certification at the bottom of the first page must be signed. Additionally, the owner or the owner’s agent is required to sign and date the form to attest to the accuracy of the information provided.
  • Check for exceptions: Be aware of any exceptions that might apply to your project, such as those for additions of 600 square feet or less, renovations, and new heating systems in existing buildings.
  • Include mandatory attachments: If your submission includes new cooling, heating, or water heating systems, make sure to attach the HVAC sizing calculation and, if applicable, duct and air leakage test reports.
  • Review component criteria: Familiarize yourself with the performance criteria for each building component as outlined in Table 402A and ensure each component in the proposed home meets or exceeds these standards.

Don'ts:

  • Overlook sealed features: Do not ignore the requirement for certain elements, like recessed lighting and windows, to be caulked, gasketed, weatherstripped, or otherwise sealed as indicated in Table 402B.
  • Exceed glass area limits: Avoid exceeding the maximum glass to conditioned floor area percentage. Standard compliance allows for up to 20%, with certain exceptions allowing more.
  • Miss programmatic requirements: Do not forget to include a programmable thermostat if a forced-air furnace is your primary heating system, as required by Section 403.1.1.
  • Skip duct insulation and testing: Overlooking the insulation and testing requirements for ducts in attics or on roofs can lead to non-compliance. Ducts require R-8 insulation, and testing to a leakage of ≤ 0.03 by a Class 1 BERS rater is mandatory.
  • Ignore water heating system requirements: Make sure to comply with the specified efficiencies and install a heat trap for vertical pipe risers associated with the water heating system.
  • Forget about lighting standards: At least 50% of permanently installed lighting fixtures must be high-efficacy lamps. Overlooking this requirement could result in non-compliance with the energy code.

By following these guidelines, you can help ensure that your project complies with the Florida Building Code, Energy Conservation. It’s always a good idea to consult with a professional if you have specific questions or concerns about your project.

Misconceptions

Understanding the Florida Energy Form can seem daunting at first glance, but once you dive into the details, it's straightforward. Let's debunk some common misconceptions that often cause confusion.

  • Only new constructions need to comply: It’s a myth that only new buildings have to adhere to the Florida Energy Form requirements. In reality, renovations, additions, and the installation of new heating, cooling, and water heating systems in existing buildings must also comply, making it applicable to a wide range of construction projects.

  • Electric resistance heating is completely prohibited: While electric resistance heating is generally discouraged due to its high energy consumption, it's not entirely banned. Exceptions are made for additions, renovations, and new heating systems in existing buildings, allowing for flexibility in certain situations.

  • All glass types and sizes are allowed: There's a misconception that you can use any type or size of glass in your construction. However, the form clearly restricts glass areas to no more than 20% of the conditioned floor area to maintain energy efficiency, with certain exceptions allowing for a maximum glass to CFA (conditioned floor area) of 50 percent for smaller additions.

  • Insulation requirements are the same for all locations: Insulation needs vary depending on the type of wall, ceiling, or floor. The form specifies different R-values (a measure of insulation's effectiveness) for various components based on their location and material, ensuring each part of the building is properly insulated.

  • Ducts don't need to be sealed or tested if they're in conditioned spaces: Regardless of their location, ducts must meet specific airtightness criteria to prevent energy losses. The form requires ducts, whether in conditioned or unconditioned spaces, to be insulated and tested to ensure they are substantially leak-free.

  • Any heating or cooling system efficiency is acceptable: This is false. To comply with the Florida Energy Code, installed heating and cooling systems must meet certain efficiency criteria detailed in the form. This ensures that only high-efficiency systems that contribute to energy conservation are used.

  • All buildings automatically comply with the Florida Energy Code: Compliance is not automatic. The building must meet or exceed the specific energy efficiency requirements and pass an inspection for compliance verification. The form serves as a tool to demonstrate compliance but does not guarantee it.

  • Hot water system requirements are universal: Hot water systems are subject to varying efficiency requirements based on their type and capacity. The form outlines specific efficiency factors (EF) for electric and gas-fired water heaters, disproving the notion that one standard applies to all.

  • No verification is needed for compliance: Actually, the form requires a certification statement to be prepared by the person filling out the form, and plans and specifications must be reviewed for compliance. Additionally, before construction is completed, the building will be inspected to ensure it meets the Florida Energy Code requirements, highlighting the importance of verification in the compliance process.

By understanding these points, individuals can better navigate the requirements of the Florida Energy Form, ensuring their building projects not only comply with legal standards but also promote energy conservation and efficiency.

Key takeaways

Understanding the Florida Energy Form is essential for professionals involved in the construction, renovation, or energy management of residential buildings in Florida. Here are key takeaways to ensure compliance and efficient energy use:

  • The Florida Energy Form is designed to demonstrate compliance with Section 402 of the Florida Building Code, Energy Conservation, applicable to single- and multiple-family residences up to three stories high, as well as renovations and system installations in existing buildings.
  • To comply, a building must meet or exceed the energy efficiency benchmarks outlined in Table 402A and adhere to all mandatory requirements summarized in Table 402B of the form.
  • Buildings featuring more than 20% glass area or electric resistance heating in attics, among other specific features, cannot use this method for compliance.
  • Small additions (less than 600 sq. ft.), renovations, and equipment changes are allowed certain exceptions under this compliance method.
  • All inputs in the "To Be Installed" column on Table 402A must either match or surpass the listed requirements for energy efficiency.
  • Table 402B mandates a checklist approach, where each applicable requirement must be checked off to indicate planned compliance.
  • The completion and signing of the "Prepared By" certification at the bottom of the first page are mandatory. This must be done by the owner or the owner’s authorized agent.
  • The form requires detailed information about the building's construction elements, including windows, doors, insulation, HVAC systems, and water heating systems, ensuring that each component meets specific energy performance criteria.
  • If a building cannot comply using this form or its alternate, Section 405 of the Florida Building Code, Energy Conservation, offers another pathway for compliance, typically involving more detailed energy modeling.

Completion and adherence to the Florida Energy Form not only affirm compliance with state energy codes but also contribute to the broader goal of promoting energy-efficient building practices in Florida. Proper use of this form can significantly impact the energy consumption and overall sustainability of residential buildings throughout the state.

Please rate Fill Out a Valid Florida Energy Template Form
4.69
Excellent
175 Votes